DUCT DETECTOR:
- 24 VAC/DC or 120 VAC.
The InnovairFlex D4120 4-wire photoelectric duct smoke detector features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork.
This unit senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of –4°F to 158°F, and a humidity range of 0 to 95 percent (non-condensing).
A plug-in sensor head offers improved false alarm immunity and simple installation, testing, and maintenance. An improved cover design isolates the sensor head from the low-flow feature for simple maintenance.
SAMPLING TUBE:
- 1.5′ / 18 inches – For use in Supply or Return Ducts.
The DST family of sampling tubes are pieces of steel piping with a series of holes drilled the entire length of the tube and should extend the entire width of the duct. The correct length has to be chosen for width of the duct where it will be installed. The sampling tube length must extend at least 5/8 across the duct width for optimal performance. The sampling tube is always installed with the air inlet holes facing into the air flow. The tubes lock securely into place and can be removed by releasing the front or rear locking tab.